Testing Capacity | 0 – 2000kW |
Type of Load | Resistive type, Power factor 1.0 |
Duty | Continuous |
Cooling System | forced air cooled by industrial grade axial fan |
Phase | 3 Phase Rated |
Rated Testing Voltage | AC 3P4W, 380V |
Rated Frequency | 50Hz/60Hz |
Working Mode | load step control Total testing capacity ranges from 0 to max load consisting of 10kw, 20kw, 50kw,100KW load setting switches, from 0-2000kw, any load combination is achievable. Load step resolution is 10kw. |
Type of control | 1. Manual switch knobs control 2. Touch screen control 3. Remote control through laptop |
Parameter Measuring Accuracy Grade | 0.5 |
Load Control Accuracy | ±5% |
Load Bank Protection | Overheating protection, cooling fans failure protection and over load protection with alarm. |
Operating Environment | Altitude:≦2500m above sea level. Ambient Temp:-10℃ ~ +55℃ Relative Humidity:≦98% ventilated environment without explosive or corrosive dust. Extra roof needed if you need to use in rainy outdoor. |
Weight | 8200 kg |
Dimensions (mm) | Standard 20‘ container |